When Are Your Fire Safety Services due?
Not sure how frequently you need to have particular services performed? Check out below and stay up-to-date for maximum performance and safety.
-
INSPECTION
Gauges (dry, preaction, deluge) > Weekly / monthly
Control valves > Weekly / monthly
Waterflow devices > Quarterly
Valve supervisory devices > Quarterly
Supervisory signal devices > Quarterly
Gauges (wet pipe) > Monthly
Hydraulic nameplate > Quarterly
Buildings > Annually (prior to freezing weather)
Hanger / seismic bracing > Annually
Pipe and fittings > Annually
Sprinklers > Annually
Spare sprinklers > Annually
Fire department connections > Quarterly
Obstruction > 5 years
TESTWaterfly devices > Quarterly / semiannually
Valves supervisory devices > Semiannually
Supervisory signal devices > Semiannually
Main drain > Annually
Antifreeze solution > Annually
Gauges > 5 years
Sprinklers - extra high temp. > 5 years
Sprinklers - fast response > At 20 years and every 10 thereafter
Sprinklers > At 50 years and every 10 thereafter
MAINTENANCEValves > Annually or as needed
Obstruction investigation > 5 years or as needed
Low-point drains (dry pipe system) > Annually prior to freezing and as needed
INVESTIGATIONObstruction > As needed
-
INSPECTION
Control valves > Weekly / monthly
Pressure regulating devices > Quarterly
Piping > Annually
Hose connections > Annually
Cabinet > Annually
Hose storage device > Annually
Hose nozzle > Annually and after each use
TESTWaterflow devices > Quarterly / semiannually
Valve supervisory devices > Semiannually
Supervisory signal devices > Semiannually
Hose storage device > Annually
Hose storage device > 5 years / 3 years
Pressure control valve > 5 years
Pressure reducing valve > 5 years
Hydrostatic test > 5 years
Flow test > 5 years
Main drain test > Annually
MAINTENANCEHose connections > Annually
Valves > Annually / as needed
-
INSPECTION REQUIREMENTS
Control Valves - Sealed > Weekly
Control Valves - Locked > Monthly
Control Valves - Tamper switches > Monthly
Alarm Valves - Exterior > Monthly
Alarm Valves - Interior > 5 years
Alarm Valves - Strainers, filters, orifices > 5 years
Preaction / Deluge Valves - Enclosure (during cold weather) > Daily / weekly
Preaction / Deluge Valves - Exterior > Monthly
Preaction / Deluge Valves - Interior > Annually / 5 years
Preaction / Deluge Valves - Strainers, filters, orifices > 5 years
Dry Pipe Valves / Quick-Opening Devices - Enclosure (during cold weather) > Daily / weekly
Dry Pipe Valves / Quick-Opening Devices - Exterior > Monthly
Dry Pipe Valves / Quick-Opening Devices - Interior > Annually
Dry Pipe Valves / Quick-Opening Devices - Strainers, filters, orifices > 5 years
Pressure Reducing and Relief Valves - Sprinkler systems > Annually
Pressure Reducing and Relief Valves - Hose connections > Annually
Pressure Reducing and Relief Valves - Hose racks > Annually
Fire pumps - Casing relief valves > Weekly
Fire pumps - Pressure relief valves > Weekly
Backflow Prevention Assemblies - Reduced pressure > Weekly / monthly
Backflow Prevention Assemblies - Reduced pressure detectors > Weekly / monthly
Fire Department Connections > Quarterly
TESTING REQUIREMENTSMain Drains > Annually / quarterly
Waterflow Alarms > Quarterly / semiannually
Control Valves - Position > Annually
Control Valves - Operation > Annually
Control Valves - Supervisory > Semiannually
Preaction / Deluge Valves - Priming water > Quarterly
Preaction / Deluge Valves - Low air pressure alarms > Quarterly
Preaction / Deluge Valves - Full flow > Annually
Dry Pipe Valves / Quick-Opening Devices - Priming water > Quarterly
Dry Pipe Valves / Quick-Opening Devices - Low air pressure alarm > Quarterly
Dry Pipe Valves / Quick-Opening Devices - Quick-opening devices > Quarterly
Dry Pipe Valves / Quick-Opening Devices - Trip test > Annually
Dry Pipe Valves / Quick-Opening Devices - Full flow trip test > 5 years
Pressure Reducing and Relief Valves - Sprinkler systems > 5 years
Pressure Reducing and Relief Valves - Circulation relief > Annually
Pressure Reducing and Relief Valves - Pressure relief valves > Annually
Pressure Reducing and Relief Valves - Hose connections > 5 years
Pressure Reducing and Relief Valves - Hose racks > 5 years
Backflow Prevention Assemblies > Annually
MAINTENANCE REQUIREMENTSCentral Valves > Annually
Preaction / Deluge Valves > Annually
Dry Pipe Valves / Quick-Opening Devices > Annually
-
Stored-pressure loaded-stream and antifreeze: 1 year
Pump tank water and pump tank calcium chloride based: 1 year
Dry chemical, cartridge- and cylinder-operated, with mild steel shells: 1 year
Dry powder, cartridge- and cylinder-operated, with mild steel shells: 1 year
Wetting agent: 1 year
Stored-pressure water: 5 years
Stored-pressure dry chemical, with stainless steel shells: 5 years
Carbon dioxide: 5 years
Wet chemical: 5 years
Dry chemical stored-pressure, with mild steel shells, brazed brass shells, and aluminum shells: 6 years
Halogenated agents: 6 years
Dry powder, stored-pressure, with mild steel shells: 6 years
-
Stored-pressure water, water mist, loaded stream, and/or antifreeze > 5 years
Wetting agent > 5 years
AFFF (aqueous film-forming foam) > 5 years
FFFP (film-forming fluoroprotein foam) > 5 years
Dry chemical with stainless steel shells > 5 years
Carbon dioxide > 5 years
Wet chemical > 5 years
Dry chemical, stored-pressure, with mild steel shells, brazed brass shells, or aluminum shells > 12 years
Dry chemical, cartridge- or cylinder-operated, with mild steel shells > 12 years
Halogenated agents > 12 years
Dry powder, stored-pressure, cartridge- or cylinder-operated, with mild steel shells > 12 years
Frequency of Internal Maintenance and Hydrostatic Testing of Fire Extinguishers
Dry chemical > Internal Maintenance: 6 years, Hydrostatic Testing: 12 years
Water, AFFF, FFFP, antifreeze > Internal Maintenance: 5 years, Hydrostatic Testing: 5 years
Halogenated agent > Internal Maintenance: 6 years, Hydrostatic Testing: 12 years
Carbon dioxide > Internal Maintenance: 5 years, Hydrostatic Testing: 5 years
-
1. Control Equipment: Fire Alarm Systems Monitored for Alarm, Supervisory, and Trouble Signals
Fuses > Initial/Reacceptance, Annually
Interfaced equipment > Initial/Reacceptance, Annually
Lamps and LEDs > Initial/Reacceptance, Annually
Primary power supply > Initial/Reacceptance, Annually
2. Control Equipment: Fire Alarm Systems Unmonitored for Alarm, Supervisory, and Trouble Signals
Fuses > Initial/Reacceptance, Weekly
Interfaced equipment > Initial/Reacceptance, Weekly
Lamps and LEDs > Initial/Reacceptance, Weekly
Primary power supply > Initial/Reacceptance, Weekly
3. Batteries
Lead-acid > Initial/Reacceptance, Monthly
Nickel-cadmium > Initial/Reacceptance, Monthly
Primary (dry cell) > Initial/Reacceptance, Monthly
Sealed lead-acid > Initial/Reacceptance, Monthly
4. Transient Suppressors >Initial/Reacceptance, Semiannually
5. Fire Alarm Control Unit Trouble Signals > Initial/Reacceptance, Weekly, Annually
6. Fiber-Optic Cable Connections > Initial/Reacceptance, Annually
7. Emergency Voice / Alarm Communications Equipment > Initial/Reacceptance, Semiannually
8. Remote Annunciators > Initial/Reacceptance, Semiannually
9. Initiating Devices
Air sampling > Initial/Reacceptance, Semiannually
Duct detectors > Initial/Reacceptance, Annually
Electromechanical releasing devices > Initial/Reacceptance, Semiannually
Fire extinguishing systems > Initial/Reacceptance, Annually
Suppression system switches > Initial/Reacceptance, Annually
Fire alarm boxes > Initial/Reacceptance, Semiannually
Heat detectors > Initial/Reacceptance, Semiannually
Radiant energy fire detectors > Initial/Reacceptance, Semiannually
Smoke detectors > Initial/Reacceptance, Semiannually
Supervisory signal devices > Initial/Reacceptance, Quarterly
Waterflow devices > Initial/Reacceptance, Quarterly
10. Guard's Tour Equipment > Initial/Reacceptance, Semiannually
11. Combination Systems
Fire extinguisher monitoring device/systems > Initial/Reacceptance, Semiannually
Carbon monoxide detectors / systems > Initial/Reacceptance, Semiannually
12. Interface Equipment > Initial/Reacceptance, Semiannually
13. Alarm Notification Appliances - Supervised > Initial/Reacceptance, Semiannually
14. Exit Marking Audible Notification Appliances > Initial/Reacceptance, Semiannually
15. Supervising Station Fire Alarm Systems - Transmitters
DACT > Initial/Reacceptance, Annually
DART > Initial/Reacceptance, Annually
McCulloh > Initial/Reacceptance, Annually
RAT > Initial/Reacceptance, Annually
16. Special Procedures > Initial/Reacceptance, Annually
17. Supervising Station Fire Alarm Systems - Receivers
DACR > Initial/Reacceptance, Annually
DARR > Initial/Reacceptance, Annually
McCulloh systems > Initial/Reacceptance, Annually
Two-way RF multiplex > Initial/Reacceptance, Annually
RASSR > Initial/Reacceptance, Annually
RARS > Initial/Reacceptance, Annually
Private microwave > Initial/Reacceptance, Annually
18. Public Fire Alarm Reporting System Transmission Equipment
Publicly accessible fire alarm box > Initial/Reacceptance, Monthly
Auxiliary box > Initial/Reacceptance, Annually
Master box:
Manual operation > Initial/Reacceptance, Monthly
Auxiliary operation > Initial/Reacceptance, Annually
-
1. Control Equipment - Building Systems Connected to Supervising Station
Functions > Initial/Reacceptance, Annually
Fuses > Initial/Reacceptance, Annually
Interfaced equipment > Initial/Reacceptance, Annually
Lamps and LEDs > Initial/Reacceptance, Annually
Primary power supply > Initial/Reacceptance, Annually
Transponders > Initial/Reacceptance, Annually
2. Control Equipment - Building Systems Not Connected to a Supervising Station
Functions > Initial/Reacceptance, Annually
Fuses > Initial/Reacceptance, Annually
Interfaced equipment > Initial/Reacceptance, Annually
Lamps and LEDs > Initial/Reacceptance, Annually
Primary power supply > Initial/Reacceptance, Annually
Transponders > Initial/Reacceptance, Annually
3. Engine-Driven Generator - Central Station Facilities and Fire Alarm Systems > Initial/Reacceptance, Annually
4. Engine-Driven Generator Public Fire Alarm Reporting System > Initial/Reacceptance, Weekly
5. Batteries - Central Station Facilities
Lead-acid type:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Specific gravity > Initial/Reacceptance, Monthly
Nickel-cadmium type:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Sealed lead-acid type:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
6. Batteries - Fire Alarm Systems
Lead-acid type:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Specific gravity > Initial/Reacceptance, Semiannually
Nickel-cadmium type:
Charger test > Initial/Reacceptance, Monthly
Load voltage test > Initial/Reacceptance, Monthly
Primary type:
Age test > Initial/Reacceptance, Monthly
Sealed lead-acid type:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
7. Power Supply - Public Fire Alarm Reporting Systems
Lead-acid type batteries:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Specific gravity > Initial/Reacceptance, Monthly
Nickel-cadmium type batteries:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Sealed lead-acid type batteries:
Charger test > Initial/Reacceptance, Monthly
Discharge test > Initial/Reacceptance, Annually
Load voltage test > Initial/Reacceptance, Monthly
Wired system - voltage tests > Initial/Reacceptance, Daily
8. Fiber-Optic Cable Power > Initial/Reacceptance, Annually
9. Control Unit Trouble Signals > Initial/Reacceptance, Annually
10. Conductors - Metallic > Initial/Reacceptance
11. Conductors - Nonmetallic > Initial/Reacceptance
12. Emergency Voice / Alarm Communications Equipment > Initial/Reacceptance, Semiannually
13. Retransmission Equipment > Initial/Reacceptance
14. Remote Annunciators > Initial/Reacceptance, Annually
15. Initiating Devices
Duct detectors > Initial/Reacceptance, Annually
Electromechanical releasing device > Initial/Reacceptance, Semiannually
Fire-extinguishing system > Initial/Reacceptance, Annually
Suppression system switches > Initial/Reacceptance, Annually
Fire - gas and other detectors > Initial/Reacceptance, Annually
Heat detectors > Initial/Reacceptance, Annually
Fire alarm boxes > Initial/Reacceptance, Semiannually
Radiant energy fire detectors > Initial/Reacceptance, Semiannually
System smoke detectors - functional test > Initial/Reacceptance, Annually
Single- and multiple- station smoke alarms > Initial/Reacceptance, Annually
Single- and multiple- station heat alarms > Initial/Reacceptance, Annually
Supervisory signal devices > Initial/Reacceptance, Annually
Waterflow devices > Initial/Reacceptance, Quarterly
Valve supervisory switches > Initial/Reacceptance, Quarterly
16. Guard's Tour Equipment > Initial/Reacceptance, Annually
17. Combination Systems
Fire extinguisher monitoring device/systems > Initial/Reacceptance, Annually
Carbon monoxide detectors / systems > Initial/Reacceptance, Annually
18. Interface Equipment and Fire Safety Functions > Initial/Reacceptance, Annually
19. Special Hazard Equipment > Initial/Reacceptance, Annually
20. Alarm Notification Appliances
Audible devices > Initial/Reacceptance, Annually
Audible textual notification appliances > Initial/Reacceptance, Annually
Visible devices > Initial/Reacceptance, Annually
21. Exit Marking Notification Appliances > Initial/Reacceptance, Annually
22. Off-Premises Transmission Equipment > Initial/Reacceptance, Annually
23. Supervising Station Fire Alarm Systems
DACT > Initial/Reacceptance, Annually
DART > Initial/Reacceptance, Annually
McCulloh > Initial/Reacceptance, Annually
RAT > Initial/Reacceptance, Annually
24. Special Procedures > Initial/Reacceptance, Annually
25. Supervising Station Fire Alarm Systems
DACR > Initial/Reacceptance, Annually
DARR > Initial/Reacceptance, Annually
McCulloh systems > Initial/Reacceptance, Annually
Two-way RF multiplex > Initial/Reacceptance, Annually
RASSR > Initial/Reacceptance, Annually
RARSR > Initial/Reacceptance, Annually
Private microwave > Initial/Reacceptance, Annually
26. Public Fire Alarm Reporting System Transmission Equipment
Publicly accessible fire alarm box > Initial/Reacceptance, Semiannually
Auxiliary box > Initial/Reacceptance, Annually
Master box:
Manual operation > Initial/Reacceptance, Annually
Auxiliary operation > Initial/Reacceptance, Annually
Would you rather download and print them for your records?
Any Questions?
Couldn’t find what you’re looking for? No worries! Feel free to drop us a line, or call anytime, 24/7.